Total solution from design to delivery, installation & Commission.
We take pleasure in introducing ourselves as one of the leading manufacturer of TRANSFORMERS for over 42 years with experience in design, manufacturing, installation & commission of Power, Distribution, Cast Resin, Furnace, Earthing & Generator transformers. Mampower expert R&D team develops one of the most advanced designs to withstand short-circuit and impulse voltage tests.
It is our commitment to provide you customize transformer as per your requirement with world class quality & economical price.
Power & Distribution Transformer
Salient Features
Advanced design to withstand short circuit forces during fault.
Step-up and Step-down transformers manufactured
Low Loss and highly efficient
Pure copper conductor made in own plant to reduce load loss
Thermally upgraded insulation paper(Class A) results in Long life of transformer
Excellent process of shrinkage and vacuum drying of coils resulting in a sturdy construction
Manufactured with prime CRGO using step-lap design for low losses
Thermal treatment of core in own annealing plant to reduce core loss
Less temperature rise of core
Low Magnetizing Current to save no-load electricity bills & capacitors for Transformer.
Inherent overloading capacity due to Low Loss, High power factor and less no-load current.
Lower PD (partial discharge) value
Lower sound level
Transformer tank is filled with oil under vacuum process.
PSR or corrugated radiator
Leak proof, pressure, and vacuum tested as per standard
Self-protected, standard protective devices as per IEC standard
Online monitoring facility (on request)
Various ratings type tested
Engineers
Design Engineers
Expert R&D team
Mangers
Logistics and Transportation Personnel
Quality Analysts
Experienced technicians
Experienced Fabricators
Power Transformer
Technical Parameter
Unit
Applied Standard
IEC - 60076
Type
Outdoor
Power Rating
MVA
Up to 20MVA
Number of Phases
3/ customer requirement
Rated Voltage, Phase to Phase
High Voltage Winding
kV
36/customer requirement
Low Voltage Winding
kV
12/customer requirement
Rated Frequency
Hz
50
Rated Insulation Level
Impulse Withstand, Full Wave
High Voltage Winding
kV
170
Low Voltage Winding
kV
75
Neutral Side
Fully insulated
AC Withstand Voltage
High Voltage Winding
kV
70
Low Voltage Winding
kV
28
Impedance Voltage at 75°C and at Nominal Ratio and 100% Rated Power
%
As per IEC 60076-5/ customer requirement
Vector Diagram (IEC 60076-4)
Dyn1/Dyn11/Ynd11/Ynd1/customer requirement
Type of Cooling
ONAN/ONAF
On load Tap- changer
Type
With oil/ vacuum switches
Rated Tap
kV
36
Tapping Range Capacity
%
(+5% to -15)% / customer requirement
Positions
9/17/ customer requirement
Temperature Rise at Rated Power Maximum Ambient Temperature 40°C
Oil by Thermometer
deg. C
55
Winding by Resistance Measurement
deg. C
60
Transformer Looses
Core Loss and Rated Voltage at Rated Frequency at Nominal Tap
Watts
As per design/Customer requirement
Copper Loss at Full Load, at Rated Frequency
Watts
As per design/Customer requirement
Overall Dimension
mm
As per design
Overall Weight
kg
As per design
Transport Weight
kg
As per design
Distribution Transformer
Technical Specification for
Oil Filled Distribution Transformer up to36KV,5000KVA
Technical Parameter
Unit
Applied Standard
IEC - 60076
Type
Outdoor/Indoor
Power Rating
MVA
Up to 5000KVA
Number of Phases
3/ customer requirement
Rated Voltage, Phase to Phase
High Voltage Winding
kV
33/11/6.35/customer requirement
Low Voltage Winding
V
11/415/240 customer requirement
Rated Frequency
Hz
50
Rated Insulation Level
Impulse Withstand, Full Wave
High Voltage Winding
kV
170/75/60
Low Voltage Winding
kV
-
Neutral Side
Fully insulated
AC Withstand Voltage
High Voltage Winding
kV
70/28/20
Low Voltage Winding
kV
28/3
Impedance Voltage at 75°C and at Nominal Ratio and 100% Rated Power
%
As per IEC 60076-5/ customer requirement
Vector Diagram (IEC 60076-4)
Dyn1/Dyn11/Ynd11/Ynd11/customer requirement
Type of Cooling
ONAN/ONAF/customer requirement
Tap- changer
Off load Tap- changer
Rated voltage
KV
12
Tapping Range
%
+2.5% to -7.5%/+5% to -5%/+10% to -10%/ customer requirement
position
5/7/ customer requirement
On load Tap- changer
Type
With oil/ vacuum switches
Rated voltage
kV
12
Tapping Range Capacity
%
(+5% to -15)% / customer requirement
Positions
9/17 or higher
Temperature Rise at Rated Power Maximum Ambient Temperature 40°C
Oil by Thermometer
deg. C
55
Winding by Resistance Measurement
deg. C
60
Transformer Looses
Core Loss and Rated Voltage at Rated Frequency at Nominal Tap
Watts
As per design/Customer requirement
Copper Loss at Full Load, at Rated Frequency
Watts
As per design/Customer requirement
Overall Dimension
mm
As per design
Overall Weight
kg
As per design
Transport Weight
kg
As per design
Cast Resin Transformer (CRT):
Salient Features:
Self-extinguishing characteristics in case of fair
Compact and environment friendly
Easy installation
Maintenance free
Designed to withstand the highest short circuit stress that may occur during operation
High voltage coil windings are cast to prevent humidity
High resistance against overvoltage
Low decibel, high capacity and high performance
Low partial discharge
ENVIRONMENTALCLASS:E3
Transformers suitablefor heavy pollution areawith humidity above 95%
CLIMATICCLASS: C2
Transformers suitable for operation,transport and storage with ambient temperatures down to -25°c
FIRE BEHAVIORCLASS: F1
Transformers suitable for areaswith high risk of firebeing self-extinguishing
Technical Specification for
Cast Resin Transformer (CRT) up to 36KV, 30MVA KVA